ManualsBrandsSiemens ManualsSensors Air qualityCO2/VOC_sensors_QPA63...
12345678
1
958
QPA63.1 QPA63.2 QPA63.1/AUS
CO
2
/VOC Sensors
QPA63...
1958P01
1958P02
1958P03
Sensors designed for acquiring indoor air quality in rooms or air ducts.
Microprocessor-based units consisting of a selective photo-acoustic CO
2
sensor
and a VOC
1)
sensor with a heated stannic dioxide semiconductor.
Operating voltage AC 24 V, output signals DC 0...10 V.
1) VOC = volatile organic compounds (also called mixed gas)
Use
In ventilation and air conditioning plants to enhance room comfort and to optimize en-
ergy consumption by providing demand-controlled ventilation.
The sensor acquires the following:
• CO
2
concentration as an indicator of occupancy in rooms where smoking is
prohibited
• VOC concentration as an indicator of combustible gases and odors (tobacco smoke,
body odor, material fumes) in the room air
The sensor can be used:
• As a room sensor to acquire indoor air quality
• As a duct sensor in conjunction with the ARG64 duct mounting kit to acquire extract
air quality
The sensor is not suited for use in air ducts on the rooftop (solar radiation).
CM1N1958E
09.06.2006
Building Technologies
HVAC Products